    Contactors and Thermal Overload Relays

    DEC SERIES 3 POLE CONTACTORS (AC3)

    ContactorsFEATURES

    • CSA, CE, UL(listed)
    • C/W instantaneous auxiliary contact
    • Temperature range of -20°C to +85°C
    • Combi Head Ready to Tighten Screws
    • Compact design
    • Heavy duty pure silver point contact
    • IP20 finger protected screws

    SPECIFICATIONS

    Click on the product codes below to see individual product details: 

    Product Code*
    Unit
    Wt. (kg)
    L
    (mm)
    W
    (mm)
    H
    (mm)
    Temp
    Range
    Instant Aux. Contacts AC1 duty Ø≤40°C Rtd. Op. Power AC-3 - 3 Phase
    N/O N/C A-lth A-le 240V
    kw/HP
    380V
    kw/HP
    400V
    kw/HP
    440V
    kw/HP
    575V
    kw/HP
    DEC-11D10/240VAC 0.35 69.3 45.3 79 -25°C
    to
    +55°C
    1 - 25 12 3.0/4.0 5.5/7.5 5.5/7.5 5.5/7.5 5.5/7.5
    DEC-12D10/240VAC 0.35 69.3 45.3 79 1 - 25 16 4.0/5.5 7.5/10 7.5/10 7.5/10 7.5/10
    DEC-18D10/240VAC 0.38 69.3 45.3 84.5 1 - 32 22 5.5/7.5 11/15 11/15 11/15 11/15
    DEC-2510/240VAC 0.525 77 56.5 95.5 1 - 40 32 7.5/10 15/20 15/20 15/20 15/20
    DEC-35D10/240VAC 0.55 77 56.5 100 1 - 50 42 11/15 19/25 19/25 19/25 19/25
    DEC-45D11/240VAC 1.1 129.3 75 115 1 1 60 55 15/20 30/40 30/40 30/40 30/40
    DEC-55D11/240VAC 1.1 129.3 75 115 1 1 80 65 19/25 33/45 33/45 33/45 33/45
    DEC-65D11/240VAC 1.1 129.3 75 115 1 1 90 80 22/30 37/50 37/50 37/50 37/50
    DEC-80D11/240VAC 1.43 129 81.7 123 1 - 125 105 25/35 45/60 45/60 55/75 55/75
    DEC-100D11/240VAC 1.43 129 81.7 123 1 1 130 110 30/40 55/75 55/75 55/75 60/80

     *Coil voltages of 110V and 415V are also available. Change part number suffix to /110VAC or /415VAC as appropriate.

    DETH SERIES THERMAL OVERLOAD RELAYS

    Thermal Overload RelaysCompensated and differential overload relays with 1 N/O + 1 N/C electrically separated auxiliary contacts for direct connection with DEC series contactors.

    FEATURES

    • Screw terminals IP20 finger protected.
    • C/W Lockable & Sealable MAN/AUTO Switch.
    • Combi Head Ready open terminals ready to tighten screws.
    • 1 minute self reset when tripped.
    • Lightweight and simple to use.

    SPECIFICATIONS

    Click on the product codes below to see individual product details: 

    Product Code
    Relay Setting
    Range RC
    (FLC) A
    Aux.
    Contacts
    Aux. contact
    Type
    Rated Insulation
    Voltage (Ui) Vac
    Rated Thermal
    Current (lth) A
    Body
    Material
    O/L Relay
    Series
    Contactor
    Type
    Unit
    Wt. (kg)
    L
    (mm)
    W
    (mm)
    D
    (mm)
    DETH-0.5 0.35 - 0.5 2 N/O + N/C 600 6 Bakelite DETH DEC-11D 0.14 93 44 77
    DETH-0.75 0.5 - 0.75 2 600 6 DEC-11D 0.14 93 44 77
    DETH-1.05 0.75 - 1.05 2 600 6 DEC-11D 0.14 93 44 77
    DETH-1.45 1.05 - 1.45 2 600 6 DEC-11D 0.14 93 44 77
    DETH-1.5 0.35 - 0.5 2 600 6 DEC-11D 0.14 93 44 77
    DETH-1.9 1.45 - 1.9 2 600 6 DEC-11D 0.14 93 44 77
    DETH-2.5 1.9 - 2.5 2 600 6 DEC-11D 0.14 93 44 77
    DETH-3 2.4 - 3 2 600 6 DEC-11D 0.14 93 44 77
    DETH-4 2.9 - 4 2 600 6 DEC-11D 0.14 93 44 77
    DETH-5 3.8 - 5 2 600 6 DEC-11D 0.14 93 44 77
    DETH-6.5 4.5 - 6.5 2 600 6 DEC-11D 0.14 93 44 77
    DETH-8 6 - 8 2 600 6 DEC-11D 0.14 93 44 77
    DETH-11 8 - 11 2 600 6 DEC-11D 0.14 93 44 77
    DETH-14 11 - 14 2 600 6 DEC-11D/12D 0.14 93 44 77
    DETH-15 10 - 15 2 600 6 DEC-12D 0.14 93 44 77
    DETH-17 14 - 17 2 600 6 DEC-12D 0.14 93 44 77
    DETH-21 17 - 21 2 600 6 DEC-18D 0.15 93 44 77
    DETH-25 21 - 25 2 600 6 DEC-18D 0.15 93 44 77
    DETH-28 24 - 28 2 600 6 DEC-25D 0.15 93 44 77
    DETH-32 26 - 32 2 600 6 DEC-25D 0.15 93 44 77
    DETH-38 30 - 38 2 600 6 DEC-35D 0.18 93 44 77
    DETH-44 36 - 44 2 600 6 DEC-35D 0.18 93 44 77
    DETH-50 33 - 50 2 600 6 DEC-45D 0.427 112 77 57*
    DETH-65 43 - 65 2 600 6 DEC-55D 0.427 112 77 57*
    DETH-80 54 - 80 2 600 6 DEC-65D 0.427 112 77 57*
    DETH-96 64 - 96 2 600 6 DEC-80D 0.427 112 77 57*
    DETH-126 85 - 126 2 600 6 DEC-100D 0.427 112 77 57*

    *Without pins

    Test Position - Turn the arrow of red reset button to Test position. When pressing the red reset button, contact N/C would be opened, contact N/O would be closed.

    Manual Position - Turn the arrow of red reset button to MAN position. When Overload Relay is not tripped state, the red reset button function is stop button. When pressing red reset button, contact N/C would be opened and contact N/O would be still opened. When Overload Relay is tripped state, contact N/C would be opened and contact N/O would be closed, now the red reset button function is reset. When pressing red reset button, contact N/C and N/O would be returned the original condition.

    Auto Position - To press red button, then it could be rotated the arrow to Auto position. As Overload Relay is not tripped state, the red reset button could be stop button. When pressing red reset button, contact N/C would be opened and contact N/O would be still opened. When Overload Relay is tripped state, contact N/C would be opened and contact N/O would be closed, the tripped relay will automatically reset itself after approx. 1 min.